6.2 Communication with Other MP Series
6.2.2 When the MP2300S Acts as Slave (ladder program which uses a MSG-RCV function)
6-29
Built-in Ethernet Communications
3.
Set connection parameters.
How to set up with a connection number 02 in the CP-218 Connection Parameter Window
c Set Local Port (the port number “10002” used in the MP2300 side, for example).
d Set the Node IP Address (the IP address “192.168.001.001” configured in the MP2300S side, for example).
e Set the Node Port (the port number “10002” configured in the MP2300S side, for example).
f Select Connect Type (TCP, for example).
g Select Extended MEMOBUS for Protocol Type.
h Select Code (BIN, for example).
Caution
When any transmission or connection parameter is changed, the change will be reflected after FLASH has been saved and the
power supply is turned ON again.