6.2 Communication with Other MP Series

6.2.2 When the MP2300S Acts as Slave (ladder program which uses a MSG-RCV function)

6-21

Built-in Ethernet Communications

„

Caution

When message functions (MSG-SND, MSG-RCV) are used with the connection number 01, disable the automatic receive func-
tion. If message functions are used while the automatic receive function is enabled, communications will not function properly.

Note: The automatic receive function with a connection number 01 is set to “Enable” by default.

5.

Click Yes in the parameter setting confirmation dialog.

„

Caution

Note that when a parameter with the same connection number is already set and you click Yes in the parameter setting confirma-
tion dialog, the setting will be overwritten by the parameter configured in the Message Communication Easy Setting Window.

6.

Check the setting values.

„

Caution

When any transmission or connection parameter is changed, the change will be reflected after FLASH has been saved and the
power supply is turned ON again.