6.4 Communication with PLC Manufactured by Mitsubishi Electric Corporation (MELSEC protocol)

6.4.2 When the MP2300S Acts as Master (I/O message communication function is used)

6-88

( 2 ) How to Set up the Remote Equipment (MELSEC Q series) to Be Connected

This section explains the MELSEC Q series side procedure to set up for connecting the MP2300S with the MELSEC Q
series.

Note: MELSEC Q series are products manufactured by Mitsubishi Electric Corporation.

Contact Mitsubishi Electric Corporation for more information.

1.

Start up GX Developer.

2.

Create a new project.

3.

Set up network parameters (MELSECNET/Ethernet).

4.

Set up Ethernet operation.

5.

Set the open setting.

„

Caution

Set up a unique IP address in the network.
For the IP address, check with your network administrator.

Table 6.25 Network Parameter Setting (example)

Setting Item

Setting Details

Network Type

Ethernet

Start I/O No.

Any

Network No.

Any

Group No.

Any

Exchange Number

Any

Mode

Online

Table 6.26 Ethernet Operation Setting (example)

Setting Item

Setting Details

Communication Data Code Setting

Binary mode communication

Initial Timing Setting

Always waiting OPEN

IP Address

192.168.1.2

Transmit Frame Setting

Ethernet (V2.0)

TCP Alive Check Setting

Any

Permit Writing during RUN

Permitted

Table 6.27 Open Setting (example)

Setting Item

Setting Details

(connection number=1)

Setting Details

(connection number=2)

Protocol

TCP

TCP

Open System

Fullpassive

Fullpassive

Fixed Buffer

Any

Any

Procedure to Communicate with Fixed Buffer

Any

Any

Pairing Open

Any

Any

Check Alive

Any

Any

Local Port Number

2715H (10005)

2716H (10006)

Remote IP Address for Communications

192.168.1.1

192.168.1.1

Remote Port Number for Communications

2715H (10005)

2716H (10006)