2.2 Basic Module

2.2.4 218IFA Module (Ethernet)

2-26

* 1. “xxxx” represents a start I/O register number specified by the 218IFA cell in the detailed field of the module config-

uration definition screen.

* 2. “xxxx” represents a start I/O register number specified by the 218IFA cell in the detailed field of the module config-

uration definition screen.

Protocol Type

Extended
MEMOBUS
MEMOBUS

Select an application layer protocol.

Extended
MEMOBUS

Code

ASCII
BIN
RTU

Select a code type for the message communication data.
Depending on protocol type, available codes are restricted as fol-
lows:

√ : Available

–: Not available

ASCII

Remote Station
Name

Up to 32 single-
byte characters
(16 double-byte
characters)

Any text can be entered as a connection comment.

Blank

Input Disable

Enable/disable

Select whether to update the input data in the I/O message commu-
nication.

enable

Output Disable

Enable/disable

Select whether to update the output data in the I/O message commu-
nication.

enable

MP2300S Head
Register Number
Data Size

IW0000 to
IW7FFF

Set a start address of the input register of the MP2300S side for stor-
ing the data read from the remote equipment.

IW xxxx

*1

OW0000 to
OW7FFF

Set a start address of the MP2300S side output register for referenc-
ing the data written in the remote equipment.

OWxxxx + 4

*2

Data Size

Varies according
to protocol type

Specify the data size (word) read from the remote equipment.

4

Specify the data size (word) written in the remote equipment.

4

Head Register
Number for the
Node Equipment

Varies according
to protocol type

Specify the register type and the start register address for the remote
equipment to read.

Varies accord-
ing to proto-
col type.

Specify the register type and the start register address for the remote
equipment to write.

Data Size of the
Node Equipment

Display only

Generally, the same value specified in MP2300S data size is shown.
By way of exception, when MELSEC is selected for communication
protocol type and a bit device such as input relay (X)/ output relay
(Y)/ internal relay (M)/ link relay (B) is selected for read register,
the display is shown in bit size.

4

Generally, the same value specified in MP2300S data size is shown.
By way of exception, when MELSEC is selected for communication
protocol type and a bit device such as input relay (X)/ output relay
(Y)/ internal relay (M)/ link relay (B) is selected for read register,
the display is shown in bit size.

4

(cont’d)

Item

Setting Range

Details

Default

Protocol Type

Overview

Extended
MEMOBUS

Yaskawa’s Extended MEMOBUS protocol.

MEMOBUS

Yaskawa’s MEMOBUS protocol.

MELSEC

Ethernet I/F protocol for the sequencer (A
series) manufactured by Mitsubishi Elec-
tric Corporation.

MODBUS/TCP

Industrial Ethernet protocol proposed by
Modieon, Inc.

Protocol Type

Code

ASCII

BIN

RTU

Extended
MEMOBUS

MEMOBUS

MELSEC

MODBUS/TCP

Advertising