Appendix G MSG-SND/MSG-RCV Functions (Ethernet)

G.1 Message Transmit Function (MSG-SND)

A-69

Appendices

( 7 ) Data Address (PARAM05)

Specify the start address of the data.
The address must be input in decimal or hexadecimal numbers.
Example: When the start address is MW01000, specify “1000 (decimal)” or “3E8H (hexadecimal).”
The valid range of usable function codes and data addresses may differ, depending on the device type and device range
of the MELSEC side.
The following table gives the valid ranges of data addresses when using MELSEC as a protocol.

Note: 1. The device range may differ according to the MELSEC sequencer even within the device range. For

more information, refer to the MELSEC manual.

2. The register number corresponding to MP2000 can be adjusted by the offset setting of the MSG-SND

function.

Table G.7 Valid Range of Data Addresses (MELSEC bit device)

Device

Device Range of

ACPU Common

Commands

Decimal/

Hexa-

decimal

Function Code

Valid Range of

Data Addresses

Corresponding Register

Number

X

X0000 to X07FF

Hexadecimal 02H: Input relay

0 to 2047

MB000000 to MB00127F

Y

Y0000 to Y07FF

Hexadecimal 01H/0FH: Coil

0 to 2047

MB000000 to MB00127F

M

M0000 to M2047

Decimal

01H/05H/0FH: Coil

2048 to 4095

MB001280 to MB00255F

M

M9000 to M9255

Decimal

01H/05H/0FH: Coil

4096 to 4351

MB002560 to MB00271F

B

B0000 to B03FF

Hexadecimal 01H/05H/0FH: Coil

4352 to 5375

MB002720 to MB00335F

F

F0000 to F0255

Decimal

01H/05H/0FH: Coil

5376 to 631

MB003360 to MB00351F

TS

TS000 to TS255

Decimal

02H: Input relay

2048 to 2303

MB001280 to MB00143F

TC

TC000 to TC255

Decimal

02H: Input relay

2304 to 2559

MB001440 to MB00159F

CS

CS000 to CS255

Decimal

02H: Input relay

2560 to 2815

MB001660 to MB00175F

CC

CC000 to CC255

Decimal

02H: Input relay

2816 to 3071

MB001760 to MB00191F

M

M2048 to M8191

Decimal

01H/05H/0FH: Coil

8192 to 14335

MB005120 to MB00895F

Table G.8 Valid Range of Data Addresses (MELSEC word device)

Device

Device Range of

ACPU Common

Commands

Decimal/

Hexa-

decimal

Function Code

Valid Range of

Data Addresses

Corresponding Register

Number

TN

TN000 to TN255

Decimal

04H/0AH:
Input register

0 to 255

MW00000 to MW0255

CN

CN000 to CN255

Decimal

04H/0AH:
Input register

256 to 511

MW00256 to MW00511

D

D0000 to D1023

Decimal

03H/06H/09H/0BH/
0EH/10H:
Holding register

0 to 1023

MW00000 to MW01023

D

(special)

D9000 to D9255

Decimal

03H/06H/09H/0BH/
0EH/10H:
Holding register

1024 to 1279

MW01024 to MW01279

W

W0000 to W03FF

Hexadecimal

03H/06H/09H/0BH/
0EH/10H:
Holding register

1280 to 2303

MW01280 to MW02303

R

R0000 to R8191

Decimal

03H/06H/09H/0BH/
0EH/10H:
Holding register

2304 to 10495

MW02304 to MW10495

D

D1024 to D6143

Decimal

03H/06H/09H/0BH/
0EH/10H:
Holding register

10496 to 15615

MW10496 to MW15615

Advertising