5.4 Self-configuration

5.4.1 How to Execute Self-Configuration

5-42

5.4.1 How to Execute Self-Configuration

The following two methods are available for executing the self-configuration.

• Execute the self-configuration (from DIP switch)
• Execute the self configuration (from MPE720)

Now, this section explains each way to execute the self-configuration.

( 1 ) Procedure Using the DIP Switch

Self-configuration can be executed from the Basic Module DIP switch.

[ a ] When Executing the Self-Configuration First Time after Connecting Equipment

By performing the operation below, the self-configuration for all modules is newly executed, and all new definition
files are created.
Before performing the operation, turn ON the power supply of equipment such as SERVOPACK.

„

Caution

Note that this operation can clear the following data in MP2300S.
• All definition files, all user programs, and all registers

1. Turn OFF the power supply.

Turn OFF the 24-VDC power supply to the MP2300S.

ޓ

2. Set the DIP switch.

Set the switches INIT and CNFG of the DIP switch SW1 on the MP2300S
Basic Module to ON.

ޓ

3. Turn ON the power supply.

Turn ON the 24-VDC power supply to the MP2300S.

4. Check the LED indicators.

Check that the LED indicators on the MP2300S Basic Module change as
follows.

5. Reset the DIP siwtch.

Set the switches INIT and CNFG of the DIP switch SW1 on the MP2300S
Basic Module to OFF.

ޓ

STOP
SUP
INIT
CNFG
MON

TEST

STOP
SUP
INIT
CNFG
MON

TEST

RDY
ALM

MTX

TRX

RUN

ERR
BAT

IP

RDY
ALM
MTX
TRX

RUN

ERR
BAT

IP

RDY
ALM
MTX
TRX

RUN

ERR
BAT

IP

ڎ

ڎ

: Lit : Unlit : Blinking