2 self configuration, Mp2300s, Check that the σ-iii servopack power supply is on – Yaskawa MP2300S Basic Module User Manual
Page 121: System start up and easy programming, Option

4.2 Preparation (step 1)
4.2.2 Self Configuration
4-5
System Start Up and Easy Programming
4.2.2 Self Configuration
Run the self configuration to automatically recognize devices connected to the MECHATROLINK connector.
Steps for self configuration are as follows.
1.
Check that the
Σ-III SERVOPACK power supply is ON.
2.
Turn OFF the MP2300S 24-V power supply.
3.
Turn ON “INIT” and “CONFIG” of DIP switch (SW1) on the MP2300S main unit.
4.
Turn ON the 24-VDC power supply on the MP2300S main unit, and confirm the LED display changes
as follows:
5.
Self configuration is complete, and MECHATROLINK slave device information has been written to a
definition information file.
6.
Turn OFF “INIT” and “CONFIG” of DIP switch (SW1) on the MP2300S main unit.