System Status

System operating status and error status is stored in registers SW00040 to SW00048. Checking of system status details
are used to determine whether hardware or software is the cause of an error.

Name

Register No.

Description

Reserved by
the system.

SW00030

to

SW00039

CPU Status

SW00040

SB000400

READY

0: Failure, 1: Normal

SB000401

RUN

0: Stopped, 1: Running

SB000402

ALARM

0: Normal, 1: Alarm

SB000403

ERROR

0: Normal, 1: Error

SB000404

Reserved by the system.

SB000405

Reserved by the system.

SB000406

FLASH

1: Flash operation

SB000407

WEN

0: Write-disabled, 1: Write-enabled

SB000408

to

SB00040D

Reserved by the system.

SB00040E

Operation Stop Request

0: RUN selection, 1: STOP selection

SB00040F

Run Switch Status at Power ON

0: STOP, 1: RUN

CPU Error
Status

SW00041

SB000410

Serious Failure

1: WDGE, undefined command
See SW00050 for details.

SB000411

Reserved by the system.

SB000412

Reserved by the system.

SB000413

Exception Error

SB000414

to

SB000417

Reserved by the system.

SB000418

User operation error

1: User operation error

SB000419

I/O Error

1: I/O error

SB00041A

to

SB00041F

Reserved by the system.

H Scan Over
Counter

SW00044

L Scan Over
Counter

SW00046

Reserved by
the system.

SW00047

Reserved by the system.

Hardware
Configuration
Status

SW00048

SB000480

TEST

DIP switch alarms
0: ON, 1: OFF

SB000481

MON

SB000482

CNFG

SB000483

INIT

SB000484

SUP

SB000485

STOP

SB000486

SB000487

Battery Alarm

SB000488

to

SB00048F

Reserved by the system.

Reserved by
the system.

SW00049

SW000490

to

SW00049F

Reserved by the system.