6.3 Communication with Touch Panel

6.3.1 When the MP2300S Acts as Slave (automatic receive function is used)

6-69

Built-in Ethernet Communications

5.

Click Yes in the parameter setting confirmation dialog box.

„

Caution

Note that when a parameter with the same connection number is already set and you click Yes in the parameter setting confirma-
tion dialog, the setting will be overwritten by the parameter configured in the Message Communication Easy Setting Window.

6.

Check the setting value and click the Detail Button in the Automatically column.

7.

Check Enable in the Automatically Reception Setting Window and then click the OK Button.

Note: For more information on Slave Side I/F Register Setting and Automatic Receive Process Delay Time,

refer to 2.2.4 ( 4 ) (b)

„

Automatic Receive Setting Screen for Message Communication .

The automatic receive function for connecting the MP2300S to the touch panel is now set up.

„

Caution

When any transmission or connection parameter is changed, the change will be reflected after FLASH has been saved and the
power supply is turned ON again.