Appendix H Optional Functions

H.2 Security

A-128

( 7 ) Security-related System Registers

The security setting status can be checked by using the following system registers.

( 8 ) Application Precautions

• The security settings data is saved in flash memory.

When starting from flash memory, an operation will be performed according to the status when data was saved to
flash memory. Therefore, be sure to save the data to flash memory after making the security settings if the Con-
troller will be started from flash memory.

• Security function does not apply when offline (i.e., when the MPE720 is used alone).

You cannot make security settings even if you log on offline. Manage offline data so that applications are pro-
tected from being disclosed.

• Always enter at least one alphanumeric character for the security key.

To ensure security, at least one alphanumeric character must be entered in the security key. Although no key can
guarantee foolproof security, you can increase the security of your key by entering a mixture of uppercase, low-
ercase, and numeric characters (e.g., A to Z, a to z, and 0 to 9).

Name

Register Number

Description

Security Status

SW00506

0: No security, 1: Security set

Security Reading
Restriction Information

SW00507

SB005070 to SB005073

File Reading Restriction Privilege
SW00507=***xH
x: Restriction privilege level (0 to 7)

SB005074 to SB005076

Reserved by system.

SB005077

0: File reading not restricted
1: File reading restricted

SB005078 to SB00507F

Reserved by system.