2.2 Basic Module

2.2.4 218IFA Module (Ethernet)

2-19

Specifications and Functions

„

Detailed Setting Screen of Transmission Parameter Setting

Sets the engineering communication with MPE720 and the message communication.

The following table shows each setting item.

Item

Setting Range

Details

Default

Engineering Port

256 to 65535

Specify the port number for the 218IFA module used in the engineer-
ing communication with MPE720.
Note: When changing this setting, you must also change the engineer-
ing port value in the logical port setting detailed screen of the MPE720
communication process.
The port number cannot be 9998 or 10000.

9999

Response Time
(Response moni-
tor period)

0 to 255

(sec)

Specify the wait time until a remote response is returned after sending
a command, when carrying out a message communication using MSG-
SND function. (value zero waits infinitely.)
If the retransmit number of times is zero, set response monitor period
to zero.
Note: If no response is returned after the setting period expires, a time-

out occurs, retry the transmission the number of times specified
by resend number of times.

0

Count of Retry

0 to 255

(time)

Specify the command retransmit number of times when a timeout is
detected after response monitor period expires.
Note: If no response is returned after as many retries as the retransmit

number of times, an error is returned to the MSG-SND function.

0