A-96, 4 ) connection number (param02) – Yaskawa MP2300S Basic Module User Manual

Page 418

Advertising
background image

Appendix G MSG-SND/MSG-RCV Functions (Ethernet)

G.2 Message Receive Function (MSG-RCV)

A-96

[ d ] PARAMETER (parameter)

When RESULT(process result) = 4 (FMT_NG: parameter format error), an error code in the table below is output. Oth-
erwise, the connection number is output.

( 4 ) Connection Number (PARAM02)

Specify the remote source.
When the communication device is Ethernet (218IF or 218IFA), set the connection number.
The following table shows the setting range.

Note: When the communication device is Ethernet (218IF or 218IFA), set the connection number in accor-

dance with the connection number in the 218IF or 218IFA Parameter Setting Window for the MPE720
module configuration definition.

Fig. G.10 218IFA Parameter Setting Screen for the MPE720 Module Configuration Definition Window

RESULT (process result)

Code (Hex)

Meaning

When RESULT (process re-

sult) =4

(FMT_NG: parameter format

error)

00

No error

01

Connection number is out of range

02

Time error for monitoring to receive MEMOBUS response

03

Error in setting retransmit count

04

Error in setting cyclic area

05

CPU number error

06

Data address error

07

Data size error

08

Function code error

Others

xx

Connection number

Communication Device

Connection

Number

Remarks

Ethernet (218IF)

1 to 20

Receives from the remote station set for the specified connection number.

Ethernet (218IFA)

1 to 4

Same as above

Advertising