Appendix G MSG-SND/MSG-RCV Functions (Ethernet)

G.1 Message Transmit Function (MSG-SND)

A-58

( 2 ) Process Result (PARAM00)

Process result is output to the upper byte. Lower byte is used for system analysis.

When an error occurs, take corrective action by referring to the following error contents:

Value of Process

Result

Meaning

00††H

In process (Busy)

10††H

Process completed (Complete)

8y††H

Error occurred (Error)

Value of

Process Result

Error Contents

Description

80††H

Reserved

81††H

Function code error

Unused function code was transmitted or received.
Check PARAM04 (function code).

82††H

Error in setting address

The following setting is out of the setting range. Check the setting.
PARAM05 (data address)
PARAM08 (coil offset)
PARAM09 (input relay offset)
PARAM10 (input register offset)
PARAM11 (holding register offset)

83††H

Data size error

The transmit or receive data size is out of the setting range.
Check PARAM04 (data size).

84††H

Error in setting circuit number

The circuit number is out of the setting range.
Check Cir-No (circuit number) of the MSG-SND function.

85††H

Error in setting channel number

The communication buffer channel number is out of the setting range.
Check Ch-No (communication buffer channel number) of the MSG-SND
function.

86††H

Connection number error

The connection number is out of the setting range.
Check PARAM02 (connection number).

87††H

Reserved

88††H

Communication section error

An error response was returned from the communication section (commu-
nication device). Check the equipment connection.
In addition, confirm communication with the remote device.

89††H

Device select error

Unavailable device is set.
Check Dev-Typ (communication device type) of the MSG-SND function.

Advertising