Mandatory, Warning, Caution – Yaskawa MP930 User Manual

Page 11

Advertising
background image

xii

Mandatory

D

Always use the ground the FG terminal to a ground resistance 100 Ω or less.
Failure to ground the MP930 may result in electrical shocks or malfunctioning.

Select, separate, and lay external cables correctly.

D

Consider the following items when selecting the I/O signal lines (external cables) to connect the
MP930 Module to external devices.

S

Mechanical strength

S

Noise interference

S

Wiring distance

S

Signal voltage, etc.

D

Separate the I/O signal lines from the power lines both inside and outside the control panel to re-
duce the influence of noise from the power lines.
If the I/O signal lines and power lines are not separated properly, malfunctioning may result.

Power

circuit

cables

Example of Separated External Cables

General

control cir-

cuit cables

Digital I/O

signal

cables

Steel separator

J

Application Precautions

WARNING

D

Do not touch any Module terminals when the system power is ON.
There is a risk of electrical shock.

Caution

D

Do not attempt to modify the MP930 programs, force outputs, switch between RUN and STOP, or
performed other similar operations while the MP930 is operating without knowing the direct and
indirect consequences of the operation.
Incorrect programming or operation may damage the equipment or cause an accident.