4 system register configuration, Jsystem status – Yaskawa MP930 User Manual
Page 269

Troubleshooting
9.2.4 System Register Configuration
9 -10
9.2.4 System Register Configuration
J
System Status
System status indicates the operating status and error details for the system. System status de-
tails are used to determine whether hardware or software is the cause of an error.
Table 9.1 System Status List
Name
Register No.
Contents
Reserved for
the System
SW00030 to
SW00039
(Not used)
CPU Status
SW00040
SB000400
READY
1: Normal, 0: Communications/Self-diagno-
sis error
SB000401
RUN
1: Running, 0: Stopped
SB000402
ALARM
1: Alarm, 0: Normal
SB000403
ERROR
1: Error, 0: Normal
SB000404
RESUME
1: Continued startup operation
0: New startup operation
SB000405
START STATUS
1: Restoration from power interruption
0: Ordinary restoration
SB000406
Reserved by system.
(Not used)
SB000407
WEN
1: WRITE enabled, 0: WRITE disabled
SB000408
Reserved by system.
(Not used)
SB000409
SB00040A
SB00040B
SB00040C
SB00040D
SB00040E
OPERATION STOP RE-
QUEST
1: STOP selection, 0: RUN selection
SB00040F
Reserved by system.
(Not used)
9