Monitor Parameter Alarm List
D -4
D.2 Setting Errors in Fixed and Setting Parameters
The following table shows the parameter No.1 operation status (bit 1 and bit 2).
Register Number
Bit
Alarm Name
Cause
Action
IWxx00
b1: PRMERR
Setting parameter
setting error
A setting that exceeds the setting
range has been made in a setting pa-
rameter.
Reset the setting parameter.
b2: FPRMERR Fixed parameter
setting error
A setting that exceeds the setting
range has been made in a fixed pa-
rameter.
Reset the fixed parameter.
The parameter number in which the setting range error has occurred can be identified using IWxx0
(Range Exceeded Parameter No.).
Parameter Number
Name
Register Number
Description
Remarks
11
Range exceeded pa-
rameter No.
IWxx0
S
When a setting that exceeds the setting
range has been made in a fixed parame-
ter or a setting parameter, the last pa-
rameter number in which a setting
range error occurred is stored.
S
Setting parameters: 1 to 47
S
Fixed parameters: 101 to 127