Jmotion parameter: alarm ilxx22 details – Yaskawa MP930 User Manual

Page 285

Advertising
background image

Troubleshooting

9.3.2 Processing Flow When a Motion Error Occurs

9 -26

Name

Contents

Alarm Code

Axis Alarm* 80h

Logic-controlled axis use prohibited

81h

Value exceeding POSMAX specified at Infinite Length Mode Axis
specification.

82h

Distance the axis traveled exceeds LONG_MAX

83h

Illegal control mode

84h

Duplicate motion commands

85h

Duplicate motion command response

86h

Illegal motion command mode

87h

Outside the VEL data range setting

88h

Outside the INP data range setting

89h

Outside the ACC/SCC/SCC data range setting

* Axis numbers are stored in bits 8 to 11 when an axis alarm occurs.

J

Motion Parameter: Alarm ILxx22 Details

The following tables lists the axis alarm flags (ILxx22).

Parameter No.

Contents

Remarks

b0: SVERR

Servo Amp error

S

Servopack alarm detected: See IWxx24 for alarm details.

Servo OFF

b1: OTF

Positive direction overtravel

S

Servo Amp overtravel in the positive direction detected (P_OT signal ON)

b2: OTR

Negative direction overtravel

S

Servo Amp overtravel in the negative direction detected (N_OT signal ON)

b3: SOTF

Positive direction software limit

S

Machine movement toward the positive software limit range detected

b4: SOTR

Negative direction software limit

S

Machine movement toward the negative software limit range detected

b5: SVOFF

Servo power supply incomplete

S

A move was executed with the servo OFF.

Servo OFF

9