3.14 Vdc control

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

103

significant enough. The motors may no longer be able to maintain their setpoint speed or the

acceleration/braking phases are prolonged.
The Vdc controller is an automatic P controller that influences the torque limits. It only

intervenes when the DC link voltage approaches the "upper threshold" (p1244) or "lower

threshold" (p1248) and the corresponding controller is activated via the configuration

parameter (p1240).
The recommended setting for the P gain is

p1250 = 0.5*DC link capacitance [mF].
Once the DC link has been identified (p3410), the DC link capacitance can be read in

parameter p3422 in the Infeed Module.

Note
To ensure that the drives remain active if the Line Module has failed, the response to fault

F07841 must be changed to "none" or the operation message from the Infeed Module must

be permanently set to "1" with p0864.

The Vdc controller can be used, for example, when a Line Module without energy feedback

(Vdc_max controller) is used and as a safety measure in the event of a power failure

(Vdc_min and Vdc_max controller). To ensure that critical drives can be operated for as long

as possible, parameterizable faults exist that switch off individual drives if there is a problem

with the DC link.

Description of Vdc_min control (p1240 = 2, 3)

UHJHQHUDWLYH

PRWRU

,

TVHWS

73RZHU
IDLOXUH

:LWKRXW9GFBPLQFRQWURO
IDXOW)

3RZHUUHVWRUH

3RZHUIDLOXUH

QVHWS

 U

$

W

S

W

W

PLQ

9

Figure 3-21 Switching Vdc_min control on/off (kinetic buffering)

In the event of a power failure, the Line Module can no longer supply the DC link voltage,

particularly if the Motor Modules in the DC link line-up are drawing active power. To maintain

the DC link voltage in the event of a power failure (e.g. for a controlled emergency

retraction), the Vdc_min controller can be activated for one or more drives. If the voltage

threshold set in p1248 is undershot, these drives are decelerated so that their kinetic energy