Communication PROFIBUS DP/PROFINET IO

10.2 Communication via PROFIBUS DP

Drive Functions

420

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Data

Time required [µs]

Per byte of user data

1,5

One additional class 2 master

500

User data integrity

User data integrity is verified in both transfer directions (master <––> slave) by a sign-of-life

(4-bit counter).
The sign-of-life counters are incremented from 1 to 15 and then start again at 1.
● Master sign-of-life

– STW2.12 ... STW2.15 are used for the master sign-of-life.
– The master sign-of-life counter is incremented in each master application cycle

(TMAPC).

– The number of sign-of-life errors tolerated can be set via p0925.
– p0925 = 65535 deactivates sign-of-life monitoring on the slave.
– Monitoring

The master sign-of-life is monitored on the slave and any sign-of-life errors are

evaluated accordingly.
The maximum number of tolerated master sign-of-life errors with no history can be set

via p0925.
If the number of tolerated sign-of-life errors set in p0925 is exceeded, the response is

as follows:
– A corresponding message is output.
– The value zero is output as the slave sign-of-life.
– Synchronization with the master sign-of-life is started.

● Slave sign-of-life

– ZSW2.12 ... ZSW2.15 are used for the slave sign-of-life.
– The slave sign-of-life counter is incremented in each DP cycle (T