Vector control

4.20 Bypass

Drive Functions

166

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Table 4-10 Parameter setting for bypass function with synchronization with overlap

Parameter

Description

p1262 =

Bypass dead time setting

p1263 =

Debypass dead time setting

p1264 =

Bypass delay time setting

p1265 =

Speed threshold setting when p1267.1 = 1

p1266 =

Control signal setting when p1267.0 = 1

p1267.0 =

p1267.1 =

p1267.2 =

Trigger signal setting for bypass function

P1269[0] =

Signal source to provide the feedback signal of contactor K1

P1269[1] =

Signal source for contactor K2 feedback

p3800 = 1

The internal voltages are used for synchronization.

p3802 = r1261.2

Synchronizer activation is triggered by the bypass function.

Function diagrams (see SINAMICS S List Manual)

● 7020 Synchronization

Overview of key parameters (see SINAMICS S List Manual)

Bypass function

● p1260 Bypass configuration
● r1261 CO/BO: Bypass control/status word
● p1262 Bypass deadtime
● p1263 Debypass delay time
● p1264 Bypass delay time
● p1265 Bypass speed threshold
● p1266 BI: Bypass control signal
● p1267 Bypass source configuration
● p1268 BI: Bypass control signal
● p1269 BI: Bypass switch feedback signal source

Synchronization

● p3800 Sync-line-drive activation
● p3801 Sync-line-drive object number
● p3802 BI: Sync-line-drive enable
● r3803 CO/BO: Sync-line-drive control word
● r3804 CO: Sync-line-drive target frequency