Function modules

7.9 Basic positioner

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

261

CAUTION

During adjustment with the rotary absolute encoder, a range is aligned symmetrically

around the zero point with half the encoder range within which the position is restored after

switch off/on. If position tracking is deactivated (2720.0 = 0), only one encoder overflow is

permitted to occur in this range (further details are given in chapter Position controller ->

Actual position value conditioning). Once adjustment has been carried out, the range must

not be exited because a unique reference between the actual encoder value and the

mechanical components cannot be established outside the range.
If the reference point p2599 is in the encoder range, the actual position value is set in line

with the reference point during adjustment. Otherwise, it is set to a corrected value in the

encoder range.
No overflow occurs with linear absolute encoders, which means that the position can be

restored within the entire traversing range after switch on/off once adjustment has been

carried out. During adjustment, the actual position value is set in line with the reference

point.

Reference point approach for incremental measurement systems

When the reference point approach (in the case of an incremental measuring system), the

drive is moved to its reference point. In so doing, the drive itself controls and monitors the

complete referencing cycle.
Incremental measuring systems require that after the machine has been powered-up, the

absolute dimension reference is established to the machine zero point. When powering-up

the position actual value x

0

in the non-referenced state is set to x

0

= 0. Using the reference

point approach, the drive can be reproducibly moved to its reference point. The geometry

with a positive starting direction (p2604 = "0") is shown in the following.