Basic information about the drive system

12.12 System sampling times

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

529

Construction type

Number

p0112

p0115[0]

p1800

Booksize

4 kHz

Chassis

400 V / ≤ 250 kW

1 to 2 only n_ctrl

1 to 4 only V/f

1 to 2 n_ctrl and

V/f mixed

3 (Standard)

250 µs

2 kHz

Booksize

4 kHz

Chassis

400 V / ≤ 250 kW

3 to 4 only n_ctrl

5 to 6 only V/f

3 to 4 n_ctrl and

V/f mixed

0 (Expert)

500 µs

2 kHz

1 to 3 only n_ctrl

1 to 6 only V/f

1 to 3 n_ctrl and

V/f mixed

0 (Expert)

1 (xLow)

375 µs (p0092 = 1)

400 µs (p0092 = 0)

1.333 kHz

1.25 kHz

Chassis

> 250 kW

690 V

4 only n_ctrl

4 n_ctrl and V/f

mixed

0 (Expert)

1 (xlow)

500 µs (p0092 = 1)

400 µs (p0092 = 0)

2 kHz

1.25 kHz

Booksize

4 kHz

Chassis

> 6 only V/f

0 (Expert)

500 µs

2 kHz

1 to 2 only n_ctrl

1 to 4 only V/f

3 (Standard)

250 µs

4 kHz

Blocksize

> 2 n_ctrl (min. 1)

> 4 only V/f

0 (Expert)

500 µs

4 kHz

Caution
If a Power Module Blocksize is connected to a Control Unit, the sampling times of all vector drives are set according to the

rules for Power Modules Blocksize (only 250 µs or 500 µs possible).

12.12.5 Examples when changing sampling times / pulse frequencies

Example: Changing the current controller sampling time from 62.5 µs with p0112

Preconditions:

● Maximum 2 drives, Booksize format
● Servo motor control type

Procedure:

1. p0009 = 3 (not for offline operation)
2. Switch to the first servo drive object
3. p0112 = 4
4. Switch to the second servo drive object and repeat step 3.
5. p0009 = 0 (not for offline operation)
6. When STARTER is in offline mode: Download into the drive.