Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions

366

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Bit

Meaning

Comments

BICO

1

Fault active

The drive is faulty and, therefore, out of service.

The drive switches to power-on inhibit once the

fault has been acknowledged and the cause has

been remedied.

The active faults are stored in the fault buffer.

3

Fault active

0

No fault present

No active fault in the fault buffer.

BO: r2193.3

1

No OFF2 active

4

Coasting active (OFF2)

0

Coasting active (OFF2)

An OFF2 command is present.

BO: r0899.4

1

No OFF3 active

5

Fast stop active (OFF3)

0

Fast stop active (OFF3)

An OFF3 command is present.

BO: r0899.5

1

Power-on disable

A restart is only possible by means of OFF1 and

then ON.

6

Power-on disable

0

No power-up inhibit

Power-up is possible.

BO: r0899.6

1

Alarm present

The drive is operational again. No

acknowledgement necessary.

The active alarms are stored in the alarm buffer.

7

Alarm present

0

No alarm present

No active alarm in the alarm buffer.

BO: r2139.7

1

Setpoint-actual value monitoring within tolerance

band
Actual value within a tolerance band; dynamic

overshoot or shortfall permitted for t < t

max

permissible, e.g.

n = n

setp

±

f = f

setp

±, and,

t

max

can be parameterized

8

Speed

setpoint-actual value deviation

within tolerance band

0

Setpoint/actual value monitoring not within

tolerance band

BO: r2197.7

1

Control required

The PLC is requested to assume control. Condition

for applications with isochronous mode: drive

synchronized with PLC system.

9

Control requested

0

Local operation

Control only possible on device

BO: r0899.9

1

f or n comparison value reached or exceeded.

f or n comparison value reached or

exceeded

0

f or n comparison value not reached.

BO: r2199.1

10

Note:

The message is parameterized as follows:

p2141 Threshold value

p2142 Hysteresis

1

I, M or P limit not reached

11

I, M or P limit reached or exceeded

0

I, M or P limit reached or exceeded

BO: r1407.7

(inverted)