Communication PROFIBUS DP/PROFINET IO

10.2 Communication via PROFIBUS DP

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

411

References: /GH1/ SINAMICS S120 Equipment Manual for Control Units and Additional

System Components

● PROFIBUS diagnostic LED

Note
A teleservice adapter can be connected to the PROFIBUS interface (X126) for remote

diagnosis purposes.

Setting the PROFIBUS address

Two methods are available for setting the PROFIBUS address:
1. Via the PROFIBUS address switches on the Control Unit

– In this case, p0918 is read-only and simply displays the set address.
– A change is not effective until POWER ON.

2. Via p0918

– You can only use this method when all the PROFIBUS address switches from S1 to

S7 are set to ON or OFF.

– Address changes made via parameters must be saved in a non-volatile memory using

the "Copy from RAM to ROM" function.

– A change is not effective until POWER ON.

Example:
Setting the PROFIBUS address using the PROFIBUS address switches on the Control Unit.