Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

371

Bit

Meaning

Comments

BICO

Note:

The message is parameterized as follows:
p2155 Threshold value

p2140 Hysteresis
Application:

Speed monitoring.

1

4

Reserved

0

-

1

5

Reserved

0

-

1

No motor overtemperature alarm

The temperature of the motor is within the

permissible range.

No motor overtemperature alarm

0

Alarm, motor overtemperature

The temperature of the motor is greater than the set

motor temperature threshold (p0604).

BO: r2135.14

(inverted)

6

Note:

When the motor temperature threshold is exceeded, only an alarm is output initially to warn you of this. The

alarm is canceled automatically when the temperature no longer exceeds the alarm threshold.

If the overtemperature is present for longer than the value set via p0606, a fault is output to warn you of this.

Motor temperature monitoring can be switched-out via p0600 = 0.

Application:

The user can respond to this message by reducing the load. thereby preventing the motor from shutting down with

the "Motor temperature exceeded" fault after the set time has elapsed.

1 No thermal overload in power unit alarm

The temperature of the heat sink in the power

section is within the permissible range.

7

No thermal overload in power

section alarm

0 Thermal overload in power unit alarm

The temperature of the heat sink in the power unit is

outside the permissible range.

If the overtemperature remains, the drive switches

itself off after approx. 20 s.

BO: r2135.15

(inverted)

1 The speed setpoint/actual value is within the

tolerance p2163: The signal is switched on after the

delay specified in p2167 has elapsed.

8

Speed setp - act val deviation in

tolerance t_on

0 The speed setpoint/actual value is outside the

tolerance.

BO: r2199.4

1 -

9...

12

Reserved

0 -

-

1 Pulses enabled

The pulses for activating the motor are enabled.

Pulses enabled

0 Pulses inhibited

BO: r0899.11

13

Application:

Armature short-circuit protection must only be switched on when the pulses are inhibited.
This signal can be evaluated as one of many conditions when armature short-circuit protection is activated.

14

1

-

15

Reserved

0

-

-