Basic information about the drive system

12.10 Rules for wiring with DRIVE-CLiQ

Drive Functions

506

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

● The set processing and communication cycles
Below you will find the binding wiring rules and some other recommendations as well as a

few sample topologies for DRIVE-CLiQ wiring.
The components used in these examples can be removed, replaced with others or

supplemented. If components are replaced by another type or additional components are

added, the SIZER tool should be used to check the topology.
If the actual topology does not match the topology created offline by STARTER, the offline

topology must be changed accordingly before it is downloaded.

12.10.1 General rules

DRIVE-CLiQ rules

The wiring rules below apply to standard cycle times (servo 125 µs, vector 400 µs). For cycle

times that are shorter than the corresponding standard cycle times, additional restrictions

apply due to the computing power of the CU (configuration via the SIZER tool).
The rules below apply on a general basis, unless limited, as a function of the firmware

version.

Note
A Double Motor Module, a DMC20, a TM54F and a CUA32 each correspond to two DRIVE-

CLiQ participants. This also applies to Double Motor Modules, of which just one drive is

configured.

● A maximum of 14 nodes can be connected to a DRIVE-CLiQ line on the Control Unit.
● Up to 8 nodes can be connected in a row. A row is always seen from the perspective of

the Control Unit.

● Ring wiring is not permitted.
● Components must not be double-wired.
● The TM54F must not be operated on the same DQ line as Motor Modules.
● The Terminal Modules TM15, TM17 and TM41 have faster sample cycles than the TM31

and TM54F. For this reason, the two groups of Terminal Modules must be connected in

separate DRIVE-CLiQ lines.