Basic functions

6.7 Automatic restart (vector, servo, infeed)

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

189

Automatic restart mode

Table 6-6

Automatic restart mode

p1210

Mode

Meaning

0

Disables automatic restart

Automatic restart inactive

1

Acknowledges all faults without

restarting

When p1210 = 1, faults that are present are

acknowledged automatically when their cause is

rectified. If further faults occur after faults have been

acknowledged, then these are also again

automatically acknowledged. A minimum time of

p1212 + 1s must expire between successful fault

acknowledgement and a fault re-occurring if the

signal ON/OFF1 (control word 1, bit 0) is at a HIGH

signal level. If the ON/OFF1 signal is at a LOW

signal level, the time between a successful fault

acknowledgement and a new fault must be at least

1s.
For p1210 = 1, fault F07320 is not generated if the

acknowledge attempt failed (e.g. because the faults

occurred too frequently).

4

Automatic restart after line

supply failure, no additional start

attempts

For p1210 = 4, an automatic restart is only carried

out if in addition fault F30003 occurred at the Motor

Module or there is a high signal at binector input

p1208[1], or in the case of an infeed drive object

(x_Infeed) F06200 has occurred. If additional faults

are present, then these faults are also

acknowledged and when successfully

acknowledged, the starting attempt is continued.

When the 24 V power supply of the CU fails, this is

interrupted as a line supply failure.

6

Restart after any fault with

additional start attempts

When p1210 = 6, an automatic restart is carried out

after any fault or when p1208[0] = 1. If the faults

occur one after the other, then the number of start

attempts is defined using p1211. Monitoring over

time can be set using p1213.

Starting attempts (p1211) and waiting time (p1212)

p1211 is used to specify the number of starting attempts. The number is internally

decremented after each successful fault acknowledgement (line supply voltage must be re-

applied or the infeed signals that it is ready. Fault F07320 is signaled if the number of

parameterized startup attempts is exceeded.
When p1211 = x, x + 1 starting attempts are made.

Note
A start attempt immediately starts when the fault occurs.
The faults are automatically acknowledged in intervals of half the waiting time p1212.
After successfully acknowledgment and the voltage returns, then the system is automatically

powered-up again.