Basic information about the drive system

12.5 Inputs/outputs

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

485

12.5.2

Digital inputs/outputs

Digital inputs





9

;

;

',

;

S

S



U

U

;

;

0

0

0

;

0

9

9





Figure 12-9 Digital inputs: signal processing using DI 0 of CU320 as an example

Properties

● The digital inputs are "high active".
● An open input is interpreted as "low".
● Fixed debouncing setting

Delay time = 1 to 2 current controller cycles (p0115[0])

● Availability of the input signal for further interconnection

– inverted and not inverted as a binector output
– as a connector output

● Simulation mode settable and parameterizable.
● CU320: Isolation block by block, set by jumper.

– Jumper open: electrically isolated.

The digital inputs function only if a reference ground is connected.

– Jumper closed, non-floating.

The reference potential of the digital inputs is the ground of the Control Unit.

● Sampling time for digital inputs/outputs adjustable on CU320 (p0799)

Function diagrams (see SINAMICS S List Manual)

● 2020 Digital inputs, electrically isolated (DI 0 ... DI 3)
● 2120 Digital inputs, electrically isolated (DI 0 ... DI 3)
● 2121 Digital inputs, electrically isolated (DI 4 ... DI 7)