13 efficiency optimization – Efficient Networks Siemens Sinamics S120 User Manual

Page 145

Advertising
background image

Vector control

4.13 Efficiency optimization

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

145

4.13

Efficiency optimization

Description

The following can be achieved when optimizing the efficiency using p1580:
● Lower motor losses in the partial load range
● Noise in the motor is minimized

˓

VHWS

LTVHWS

S

S 

S 

S







U 

S U S U

Figure 4-20 Efficiency optimization

It only makes sense to activate this function if the dynamic response requirements of the

speed controller are low (e.g., pump and fan applications).
For p1580 = 100%, the flux in the motor under no-load operating conditions is reduced to

half of the setpoint (reference flux) (p1570/2). As soon as load is connected to the drive, the

setpoint (reference) flux linearly increases with the load and at approx. r0077 = r0331 *

p1570 reaches the setpoint set in p1570.
In the field-weakening range, the final value is reduced by the actual degree of field

weakening. The smoothing time (p1582) should be set to approx. 100 to 200 ms. Flux

differentiation (see also p1401.1) is automatically deactivated internally following

magnetization.

Function diagrams (see SINAMICS S List Manual)

● 6722 Field weakening characteristic, Id setpoint (ASM, p0300 = 1)
● 6723 Field weakening control, flux control for induction motors (p0300 = 1)

Overview of key parameters (see SINAMICS S List Manual)

● r0077 CO: Current setpoints, torque-generating
● r0331 Motor magnetizing current/short-circuit current (actual)
● p1570 CO: Flux setpoint
● p1580 Efficiency is optimization

Advertising