Communication PROFIBUS DP/PROFINET IO

10.3 Communications via PROFINET IO

Drive Functions

450

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Setting criteria for times

● Cycle (T

DC

)

– T

DC

must be set to the same value for all bus nodes. T

DC

is a multiple of SendClock.

– T

DC

> T

CA_Valid

and T

DC

≧ T

IO_Output

T

DC

is thus large enough to enable communication with all bus nodes.

NOTICE

After T

DC

has been changed on the PROFINET IO controller, the drive system must

be switched on (POWER ON) or the parameter p0972=1 (Reset drive unit) must be

set.

● T

IO_Input

and T

IO_Output

– Setting the times in T

IO_Input

and T

IO_Output

to be as short as possible reduces the dead

time in the position control loop.

– T

IO_Output

> T

CA_Valid

+ T

IO_Output_MIN

● Settings and optimization can be done via a tool (e.g. HW Config in SIMATIC S7).

User data integrity

User data integrity is verified in both transfer directions (IO controller <––> IO device) by a

sign of life (4-bit counter).
The sign-of-life counters are incremented from 1 to 15 and then start again at 1.
● IO controller sign of life

– STW2.12 ... STW2.15 are used for the IO controller sign of life.
– The IO controller sign-of-life counter is incremented on each IO controller application

cycle (T

CACF

).

– The number of sign-of-life errors tolerated can be set via p0925.
– p0925 = 65535 deactivates sign-of-life monitoring on the IO device.
– Monitoring

The IO controller sign-of-life is monitored on the IO device and any sign-of-life errors

are evaluated accordingly.
The maximum number of tolerated IO controller sign-of-life errors with no history can

be set via p0925.
If the number of tolerated sign-of-life errors set in p0925 is exceeded, the response is

as follows:
1. A corresponding message is output.
2. The value zero is output as the IO device sign of life.
3. A new synchronization with the IO controller sign of life is started.

● IO device sign of life

– STW2.12 ... STW2.15 are used as IO device sign of life.
– The IO device sign-of-life counter is incremented in each DC cycle (T

DC

).