Basic information about the drive system

12.10 Rules for wiring with DRIVE-CLiQ

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

509

Note
If an additional encoder is connected to a Motor Module, it is assigned to this drive as

encoder 2 in the automatic configuration.



960

&8



;

;

;

;

$FWLYH

/LQH

0RGXOH

;;

;;

;;

;;

;;

;;

;

6LQJOH

0RWRU

0RGXOH

Figure 12-24 Example of a topology with VSM for Booksize and Chassis components

Table 12-15 VSM connection

Component

VSM connection

Active Line Module Booksize

X202

Active Line Module (chassis)

X402

Power Modules

The VSM is not supported.

Important!
All of the nodes on the DRIVE-CLiQ line must have the same sampling time in p0115[0]. otherwise

the VSM must be connected to a separate DRIVE-CLiQ interface on the Control Unit.

● Only one final node should ever be connected to free DRIVE-CLiQ ports of components

within a DRIVE-CLiQ line (e.g. Motor Modules wired in series), e.g. one Sensor

Module or one Terminal Module without forwarding to additional components.

● If possible, Terminal Modules and Sensor Modules of direct measuring systems should

not be connected to the DQ line of Motor Modules but rather to free DRIVE-CLiQ ports of

the Control Unit.