Function modules

7.9 Basic positioner

Drive Functions

276

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

7.9.6

Direct setpoint input (MDI)

Features

● Select direct setpoint input (p2647)
● Select positioning type (p2648)
● Direction selection (p2651, p2652)
● Setting-up (p2653)
● Fixed setpoints

– CO: Position setpoint (p2690)
– CO: Velocity setpoint (p2691)
– CO: Acceleration override (p2692)
– CO: Deceleration override (p2693)

● Connector inputs

– CI: MDI position setpoint (p2642)
– CI: MDI velocity setpoint (p2643)
– CI: MDI acceleration override (p2644)
– CI: MDI deceleration override (p2645)
– CI: Velocity override (p2646)

● Accept (p2649, p2650)

Description

The direct setpoint input function allows for positioning (absolute, relative) and setup

(endless position-controlled) by means of direct setpoint input (e.g. via the PLC using

process data).
During traversing, the motion parameters can also be influenced (on-the-fly setpoint

acceptance) and an on-the-fly change can be undertaken between the Setup and Positioning

modes. The "direct setpoint input" mode (MDI) can also be used if the axis is not referenced

in the "setup" or "relative positioning" modes, which means that "flying referencing" (see the

separate section), flying synchronization, and post-referencing are possible.
The direct setpoint input function is activated by p2647 = 1. A distinction is made between

two modes: positioning mode (p2653 = 0) and setup mode (p2653 = 1).
In "positioning" mode, the parameters (position, velocity, acceleration and deceleration) can

be used to carry out absolute (p2648 = 1) or relative (p2648 = 0) positioning with the

parameter p2690 (fixed setpoint position).
In the setting-up mode, using parameters (velocity, acceleration and deceleration) "endless"

closed-loop position control behavior can be carried-out.
It is possible to make a flying changeover between the two modes.
If continuous acceptance (p2649 = 1) is activated, changes to the MDI parameters are

accepted immediately. Otherwise the values are only accepted when there is a positive edge

at binector input p2650 (setpoint acceptance edge).