Communication PROFIBUS DP/PROFINET IO

10.2 Communication via PROFIBUS DP

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

419

Name

Value

1)

Limit value

Description

MSG

Acyclic service

After cyclic transmission, the master checks whether the token

hold time has already expired. If not, another acyclic DPV1

service is transmitted.

RES

Reserve: "Active pause" until the isochronous cycle has expired

R

Processing time for speed or position controller

T

M

Master time

This is the time from the start of the position controller cycle to

the start of master closed-loop control.

GAP

Attempt to open connection with new node.
This attempt takes place every xth cycle.

T

J

T

J

returns the duration of the cycle jitter.

The cycle jitter is the delay of the GC telegram.

1) The values correspond to device master file si0280e5.gs_

Setting criteria for times

● Cycle (T

DP

)

– T

DP

must be set to the same value for all bus nodes.

– T

DP

> T

DX

and T

DP

≧ T

O

T

DP

is thus large enough to enable communication with all bus nodes.

NOTICE

After T

DP

has been changed on the PROFIBUS master, the drive system must be

switched on (POWER ON) or the parameter p0972=1 (Reset drive unit) must be set.

● T

I

and T

O

– Setting the times in T

I

and T

O

to be as short as possible reduces the dead time in the

position control loop.

– T

O

> T

DX

+ T

Omin

● A tool is available for setting and optimization purposes (e.g. HW Config in SIMATIC S7).

The following must be noted:
– Configuring reserves allows the following:

Class 2 masters can be connected
Non-cyclic communication

Minimum times for reserves

Table 10-32 Minimum times for reserves

Data

Time required [µs]

Basic load

300

Per slave

20