Vector control

4.9 Vdc control

Drive Functions

134

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

The "Vdc control" function can be activated using the appropriate measures if an overvoltage

or undervoltage is present in the DC link.
● Overvoltage in the DC link

– Typical cause

The drive is operating in regenerative mode and is supplying too much energy to the

DC link.

– Remedy

Reduce the regenerative torque to maintain the DC link voltage within permissible

limits. With the Vdc controller activated, the converter may automatically extend the

ramp down time of a drive if the shutdown supplies too much energy to the DC link.

● Undervoltage in the DC link

– Typical cause

Failure of the supply voltage or supply for the DC link.

– Remedy

Specify a regenerative torque for the rotating drive to compensate the existing losses,

thereby stabilizing the voltage in the DC link (kinetic buffering).

Properties

● Vdc control

– This comprises Vdc_max control and Vdc_min control (kinetic buffering), which are

independent of each other.

– Joint PI controller. The dynamic factor is used to set Vdc_min and Vdc_max control

independently of each other.

● Vdc_max control

– This function can be used to control momentary regenerative load without shutdown

using “overvoltage in the DC link“.

– Vdc_max control is only recommended with a supply without active closed-loop control

for the DC link and without feedback.

● Vdc_min control (kinetic buffering)

– With this function, the kinetic energy of the motor is used for buffering the DC link

voltage in the event of a momentary power failure, thereby delaying the drive.