Function modules

7.2 Technology controller

Drive Functions

222

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4







7HFBFWUW\SH

S

G

GW

7HFBFWU.S

S

7HFBFWU7Q
S







7HFBFWUO

6HWSRLQW

S

$FWXDOYDOXH

S

5DPSIXQFWLRQJHQHUDWRU

QBVHWS

S

;

VHWS

;

DFW



Figure 7-2

Fill level control: controller structure

Table 7-1

Key parameters for the level control

Parameter

Designation

Example

p1155

n_setp1 downstream of RFG

p1155 = r2294 Tec_ctrl output_sig [FP 3080]

p2200

BI: Technology controller enable

p2200 = 1 Technology controller enabled

p2253

CI: Technology controller setpoint 1

p2253 = r2224 Fixed setpoint active [FP 7950]

p2263

Technology controller type

p2263 = 1 D component in fault signal [FP 7958]

p2264

CI: Technology controller actual value

(X

ACTUAL

)

p2264 = r4055 [1] Analog input AI1 of TB30

p2280

Technology controller p-gain

p2280 Determine by optimization

p2285

Technology controller integral action time p2285 Determine by optimization

7.2.5

Integration

The technology controller function is integrated in the system as follows.

Function diagrams (see SINAMICS S List Manual)

● 7950 Fixed values (r0108.16 = 1)
● 7954 Motorized potentiometer (r0108.16 = 1)
● 7958 Closed-loop control (r0108.16 = 1)

Overview of key parameters (see SINAMICS S List Manual)

Fixed setpoints

● p2201[0..n] CO: Technology controller, fixed value 1