6.7 Automatic restart (vector, servo, infeed)

Drive Functions

188

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Overview of key parameters (see SINAMICS S List Manual)

● r0069 Phase current, actual value
● r0089 Actual phase voltage
● p1820 Direction of rotation reversal of the output phases (vector)
● p1821 Reversal of direction
● p2507 LR absolute encoder adjustment status

6.7

Automatic restart (vector, servo, infeed)

Description

The automatic restart function is used to automatically restart the drive/drive group when the

power is restored after a power failure. In this case, all of the faults present are automatically

acknowledged and the drive is powered-up again. This function is not only restricted to line

supply faults; it can also be used to automatically acknowledge faults and to restart the

motor after any fault trips. In order to allow the drive to be powered-up while the motor shaft

is still rotating, the "flying restart" function should be activated using p1200.

CAUTION

Automatic restart functions in the vector, servo mode and for infeeds with closed-loop

infeed control. After the line supply voltage is connected, Smart Line Modules 5kW/10kW

automatically power themselves up.

WARNING

If p1210 is set to the value > 1, the Line Modules / motors can start automatically once the

line supply has been reestablished. This is especially critical, if, after longer line supply

failures, motors come to a standstill (zero speed) and it is incorrectly assumed that they

have been powered-down. For this reason, entering the area around the drive when it is in

this condition can cause death, serious injury, or considerable material damage.