Efficient Networks Siemens Sinamics S120 User Manual

Page 268

Advertising
background image

Function modules

7.9 Basic positioner

Drive Functions

268

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

● An external block change p2632 "External block change" is triggered.
Traversing blocks are parameterized using parameter sets that have a fixed structure:
● Traversing block number (p2616[0...63])

Every traversing block must be assigned a traversing block number (in STARTER "No.").

The traversing blocks are executed in the sequence of the traversing block numbers.

Numbers containing the value "-1" are ignored so that the space can be reserved for

subsequent traversing blocks, for example.

● Task (p2621[0...63])

1: POSITIONING

2: FIXED ENDSTOP

3: ENDLESS_POS

4: ENDLESS_NEG

5: WAIT

6: GOTO

7: SET_O

8: RESET_O

9: JERK

● Motion parameters

– Target position or traversing distance (p2617[0...63])
– Velocity (p2618[0...63])
– Acceleration override (p2619[0...63])
– Deceleration override (p2620[0...63])

● Task mode (p2623[0...63])

The execution of a traversing task can be influenced by parameter p2623 (task mode).

This is automatically written by programming the traversing blocks in STARTER.

Value = 0000 cccc bbbb aaaa
– aaaa: Display/hide

0000: Block is not hidden

0001: Block is hidden

A hidden block cannot be selected binary-coded via binector inputs p2625 to p2630.

An alarm is output if you attempt to do so.

– bbbb: Continuation condition

0000, END: 0/1 edge at p2631

0001, CONTINUE_WITH_STOP:

The exact position parameterized in the block is approached (brake to standstill and

positioning window monitoring) before block processing can continue.

0010, CONTINUE_ON-THE-FLY:

The system switches to the next traversing block "on the fly" when the braking point

for the current block is reached (if the direction needs to be changed, this does not

occur until the drive stops within the positioning window).

0011, CONTINUE_EXTERNAL:

Same as "CONTINUE_ON-THE-FLY", except that an instant block change can be

triggered up to the braking point by a 0/1 edge. The 0/1 edge can be connected to

parameter r2526.2 of the "position control" function module, via the binector input

p2633 with p2632 = 1, or via the measuring input p2661 with p2632 = 0. Position

detection via the measuring input can be used as an accurate starting position for

relative positioning. If an external block change is not triggered, a block change is

triggered at the braking point.

0100, CONTINUE_EXTERNAL_WAIT

Control signal "External block change" can be used to trigger a flying changeover to

Advertising