Basic information about the drive system

12.10 Rules for wiring with DRIVE-CLiQ

Drive Functions

512

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Rules for FW2.4

● The Voltage Sensing Module (VSM) must be connected to a dedicated DRIVE-CLiQ port

of the Control Unit.

● If possible, the CUA31 should be connected at the end of the line.

Table 12-19 Maximum number of drives that can be controlled by a Control Unit 320

Servo

Vector V/f (=vector

without speed control

function module and

without encoder)

Vector

1 Active Line Module +

6 Motor Modules 1)

1 Active Line Module +

4 Motor Modules

1)

(sampling time of current

controller 250 µs / speed

controller 1000 µs)
1 Active Line Module +

6 Motor Modules

1

)

(sampling time of current

controller 400 µs / speed

controller 1600 µs)
1 Active Line Module +

8 Motor Modules

1)

(sampling time of current

controller 500 µs / speed

controller 4000 µs)

Number of

components

Servo and vector V/f:
1 Active Line Module + 5 Motor Modules

1)

(servo: Current controller 125 µs / speed controller

125 µs

Vector V/f:

sampling time of current controller 250 µs / speed

controller 1000 µs

with max. 2 V/f drives

sampling time of current controller 400 µs / speed

controller 1600 µs with more than 2 V/f drives)

1 Active Line Module +

2 Motor Modules

1

)

(sampling time of current

controller 250 µs / speed

controller 1000 µs)
1 Active Line Module +

4 Motor Modules

1

)

(sampling time of current

controller 400 µs / speed

controller 1600 µs)

Notes on the maximum number of drives that can be controlled by a CU320:

In addition, the "Safe Standstill" function can be activated and a TM31 connected.

No function modules must be activated.

1) If a CUA31 is connected as the first module to the Control Unit, then the maximum number is

decreased by one.