Infeed

1.3 Basic Infeed

Drive Functions

40

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

If a braking resistor has not been connected for 20 kW and 40 kW Basic Line Modules

Booksize, the braking chopper must be deactivated via p3680 = 1.

Function diagrams (see SINAMICS S List Manual)

● 8720 Control word sequential control infeed
● ...
● 8760 Messages and monitoring functions

Overview of key parameters (see SINAMICS S List Manual)

● r0002 Infeed/operating display
● r0046 CO/BO: Infeed missing enable signals
● p0210 Device supply voltage
● p0840 BI: ON/OFF1
● p0844 BI: 1. OFF2
● r0898 CO/BO: Control word sequential control infeed
● r0899 CO/BO: Status word sequence control infeed
● r2138 CO/BO: Control word, faults/alarms
● r2139 CO/BO: Status word, faults/alarms 1
● p3680 Inhibit braking chopper

1.3.2

Basic Infeed open-loop control

Description

The Basic Line Module can be controlled via the BICO interconnection by means of

terminals or the field bus. The operating status is indicated on the operating display r0002.

The missing enable signals for operation (r0002 = 00) are mapped in parameter r0046. The

EP terminals (enable pulses) must be connected in accordance with the Equipment Manual.

Acknowledge error

Errors that are still present but the causes of which have been rectified can be

acknowledged by means of a 0/1 edge at the "Acknowledge error" (p2103) signal.