2 data sets, 1 cds: command data set – Efficient Networks Siemens Sinamics S120 User Manual

Page 470

Advertising
background image

Basic information about the drive system

12.2 Data sets

Drive Functions

470

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

12.2

Data sets

12.2.1

CDS: Command Data Set

CDS: Command Data Set

The BICO parameters (binector and connector inputs) are grouped together in a command

data set. These parameters are used to interconnect the signal sources of a drive.
By parameterizing several command data sets and switching between them, the drive can

be operated with different pre-configured signal sources.
A command data set contains the following (examples):
● Binector inputs for control commands (digital signals)

– ON/OFF, enable signals (p0844, etc.)
– Jog (p1055, etc.)

● Connector inputs for setpoints (analog signals)

– Voltage setpoint for V/f control (p1330)
– Torque limits and scaling factors (p1522, p1523, p1528, p1529)

A drive object can – depending on the type – manage up to 4 command data sets. The

number of command data sets is configured with p0170.
The following parameters are available for selecting command data sets and for displaying

currently selected command data sets - e.g. in the vector mode, the following parameters are

available:
Binector inputs p0810 to p0811 are used to select a command data set. They represent the

number of the command data set (0 to 3) in binary format (where p0811 is the most

significant bit).
● p0810 BI: Command data set selection CDS bit 0
● p0811 BI: Command data set selection CDS bit 1
If a command data set that does not exist is selected, the current data set remains active.

The selected data set is displayed using parameter (r0836).