Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions

398

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Error

value

Meaning

Comment

Additional

info

0x78

Parameter %s [%s]: Write access

only in the commissioning state, drive

configuration (device: p0009 = 3).

0x79

Parameter %s [%s]: Write access

only in the commissioning state,

define drive type (device: p0009 = 2).

0x7A

Parameter %s [%s]: Write access

only in the commissioning state, data

set basis configuration

(device: p0009 = 4).

0x7B

Parameter %s [%s]: Write access

only in the commissioning state,

device configuration

(device: p0009 = 1).

0x7C

Parameter %s [%s]: Write access

only in the commissioning state,

device download

(device: p0009 = 29).

0x7D

Parameter %s [%s]: Write access

only in the commissioning state,

device parameter reset

(device: p0009 = 30).

0x7E

Parameter %s [%s]: Write access

only in the commissioning state,

device ready (device: p0009 = 0).

0x7F

Parameter %s [%s]: Write access

only in the commissioning state,

device (device: p0009 not 0).

0x81

Parameter %s [%s] may not be

written in download.

0x82

Transfer of the control authority

(master) is inhibited by BI: p0806.

0x83

Parameter %s [%s]: requested BICO

interconnection not possible

BICO output does not supply float values. The BICO input,

however, requires a float value.

0x84

Parameter %s [%s]: parameter

change inhibited

(refer to p0300, p0400, p0922)

0x85

Parameter %s [%s]: access method

not defined.

0xC8

Below the valid values.

Modification request for a value that, although within

"absolute" limits, is below the currently valid lower limit.

0xC9

Above the valid values.

Modification request for a value that, although within

"absolute" limits, is below the currently valid lower limit

(e.g. governed by the current converter rating).

0xCC

Write access not permitted.

Write access is not permitted because an access key is

not available.