Vector control

4.14 Instructions for commissioning induction motors (ASM)

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

147

Parameter

Description

Remark

p0341

Motor moment of inertia

-

p0342

Ratio between the total and motor

moment of inertia

-

p0344

Motor weight

-

p0352

Cable resistance (component of the

stator resistance)

-

p0353

Motor series inductance

-

Table 4-4

Equivalent circuit diagram for motor data

Parameter

Description

Remark

p0350

Motor stator resistance, cold

-

p0354

Motor rotor resistance, cold

-

p0356

Motor stator inductance

-

p0358

Motor rotor leakage inductance

-

p0360

Motor magnetizing inductance

-

Features

● Field weakening up to approx. 1.2 * rated speed (this depends on the drive converter

supply voltage and the motor data, also refer to limitations/ constraints)

● Flying restart (for operation without encoder, only possible with additional VSM)
● Vector closed-loop speed and torque control
● Vector V/f control for diagnostics
● Motor identification
● Speed controller optimization (rotating measurement)
● Thermal protection via temperature sensor (PTC/KTY)
● All encoders that can be connected to an SMC10, SMC20 or SMC30 are supported.
● Operation with or without encoder is possible.

Supplementary conditions

Depending on the terminal voltage and load cycle, the maximum torque can be taken from

the motor data sheets / project design instructions.

Commissioning

We recommend the following points when commissioning:
● Commissioning Wizard in STARTER

The motor identification routine and the "rotating measurement" (p1900) can be activated

from the commissioning Wizard in STARTER.