Extended setpoint channel

2.3 Jog

Drive Functions

52

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Control and status messages

Table 2-1

Jog control

Signal name

Internal control word

Binector input

PROFIdrive/Siemens

telegram 1 ... 116

0 = OFF1

STWA.0

p0840 ON/OFF1

STW1.0

0 = OFF2

STWA.1

p0844 1. OFF2

p0845 2. OFF2

STW1.1

0 = OFF3

STWA.2

p0848 1. OFF3

p0849 2. OFF3

STW1.2

Enable operation

STWA.3

p0852 Enable operation

STW1.3

Jog 1

STWA.8

p1055 Jog bit 0

STW1.8

Jog 2

STWA.9

p1056 Jog bit 1

STW1.9

Table 2-2

Jog status message

Signal name

Internal status word

Parameter

PROFIdrive/Siemens

telegram 1 ... 116

Ready to power up

ZSWA.0

r0899.0

ZSW1.0

Ready to run

ZSWA.1

r0899.1

ZSW1.1

Operation enabled

ZSWA.2

r0899.2

ZSW1.2

Power-on disable

ZSWA.6

r0899.6

ZSW1.6

Pulses enabled

ZSWA.11

r0899.11

ZSW1.11

Function diagrams (see SINAMICS S List Manual)

● 2610 Execution control - processor
● 3030 Main/added setpoint, setpoint scaling, jogging

Overview of key parameters (see SINAMICS S List Manual)

● p1055[CDS] BI: Jog bit 0
● p1056[CDS] BI: Jog bit 1
● p1058[DDS] Jog 1 speed setpoint
● p1059[DDS] Jog 2 speed setpoint
● p1082[DDS] Maximum speed
● p1120[DDS] Ramp-function generator ramp-up time
● p1121[DDS] Ramp-function generator ramp-down time

Parameterization with STARTER

The "Speed setpoint jog" parameter screen is selected with the

icon in the toolbar of the

STARTER commissioning tool: