Efficient Networks Siemens Sinamics S120 User Manual

Page 29

Advertising
background image

Infeed

1.1 Active Infeed

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

29

Switching off the controller with the OFF1 signal is delayed by the time entered in p3490.

This allows the attached drives to be braked in a controlled manner. Before the infeed is

switched off, the drives connected to the DC link should be in pulse inhibit mode.

Control and status messages

Table 1-2

Active Infeed open-loop control

Signal name

Internal control word

Binector input

Display of internal

control word

PROFIdrive telegram

370

ON/OFF1

STWAE.0

p0840 ON/OFF1

r0898.0

A_STW1.0

OFF2

STWAE.1

p0844 1 OFF2 and

p0845 2 OFF2

r0898.1

A_STW1.1

Enable operation

STWAE.3

p0852 Enable

operation

r0898.3

A_STW1.3

Disable motor

operation

STWAE.5

p3532 Disable motor

operation

r0898.5

A_STW1.5

Inhibit regenerating

STWAE.6

p3533 Inhibit

regenerating

r0898.6

A_STW1.6

Acknowledge error

STWAE.7

p2103 1 Acknowledge

or p2104

2 Acknowledge or

p2105 3 Acknowledge

r2138.7

A_STW1.7

Master ctrl by PLC

STWAE.10

p0854 Master ctrl by

PLC

r0898.10

A_STW1.10

Table 1-3

Active Infeed status message

Signal name

Internal status

word

Parameter

PROFIdrive telegram 370

Ready to power up

ZSWAE.0

r0899.0

A_ZSW1.0

Ready to run

ZSWAE.1

r0899.1

A_ZSW1.1

Operation enabled

ZSWAE.2

r0899.2

A_ZSW1.2

Fault active

ZSWAE.3

r2139.3

A_ZSW1.3

No OFF2 active

ZSWAE.4

r0899.4

A_ZSW1.4

Power-on disable

ZSWAE.6

r0899.6

A_ZSW1.6

Alarm present

ZSWAE.7

r2139.7

A_ZSW1.7

Master ctrl by PLC

ZSWAE.9

r0899.9

A_ZSW1.9

Pre-charging completed

ZSWAE.11

r0899.11

A_ZSW1.11

Line contactor energized feedback

ZSWAE.12

r0899.12

A_ZSW1.12