Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions

404

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

● Subindex:

0 dec ––> ID for the first array element.

1. parameter value ... 4th parameter value

● Format:

07 hex ––> Data type Unsigned32
08 hex ––> Data type FloatingPoint

● No. of values:

01 hex ––> A value is written to each parameter in the specified format.

● Value:

BICO input parameter: enter signal source.
Adjustable parameter: enter value

2. Invoke the parameter request.
3. Evaluate the parameter response.

Parameter response

Offset

Request reference mirrored

= 40 hex

Response ID = 02 hex

0

Response header

Axis mirrored = 02 hex

No. of parameters = 04 hex

2

Information about the parameter response:

● Request reference mirrored:

This response belongs to the request with request reference 40.

● Response ID:

02 hex ––> Write request positive

● Axis mirrored:

02 hex ––> The value matches the value from the request.

● No. of parameters:

04 hex ––> The value matches the value from the request.