6.4 Sinusoidal filter

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

185

CAUTION

If a drive in a Safety Integrated line-up is deactivated via p0105, r9774 is not read

correctly because the signals from the deactivated drive are no longer updated.
Remedy: Remove this drive from the group before you deactivate it. See also: Function

Manual (FH1), chapter Safety Integrated

Overview of key parameters (see SINAMICS S List Manual)

● p0105 Activate/deactivate drive object
● r0106 Drive object active/inactive
● p0125 Activate/de-activate power unit component
● r0126 Power unit component active/inactive
● p0145 Activate/deactivate encoder interface
● r0146 Encoder interface active/inactive
● p9495 BICO response to de-activated drive objects
● p9496 Re-establish BICO to the now activated drive objects
● r9498[0 ... 29] BICO BI/CI parameter to de-activated drive objects
● r9499[0 ... 29] BICO BO/CO parameter to de-activated drive objects

6.4

Sinusoidal filter

Description

The sinusoidal filter limits the rate of rise of voltage and the capacitive charge/discharge

currents that usually occur with inverter operation. They also prevent additional noise caused

by the pulse frequency. The service life of the motor is the same as that with direct line

operation.

CAUTION

If a sinusoidal filter is connected to the converter, the converter must be activated during

commissioning to prevent the filter from being destroyed.

Usage restrictions for sinusoidal filters

The following restrictions must be taken into account when a sinusoidal filter is used:
● The output frequency is limited to a maximum of 150 Hz.
● The modulation type is permanently set to space vector modulation without

overmodulation. This reduces the maximum output voltage to approx. 85 % of the rated

output voltage.