Basic information about the drive system

12.4 BICO technology: interconnecting signals

Drive Functions

480

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

%2%LQHFWRURXWSXW

&2&RQQHFWRURXWSXW

6LJQDOVRXUFH

%,%LQHFWRULQSXW

&,&RQQHFWRULQSXW

6LJQDOVLQN

&2 ZLWKRXWLQGH[

&2 ZLWKLQGH[

U

,QGH[ >@

U
U

>@
>@

U

>@

U

%2

U

S[[[[\



%,

S[[[[\

>@

&,

S[[[[\



&,

Figure 12-5 Interconnecting signals using BICO technology

Note
A connector input (CI) cannot be interconnected with any connector output (CO, signal

source). The same applies to the binector input (BI) and binector output (BO).

For each CI and BI parameter, the parameter list shows under "data type" the information

on the data type of the parameter and the data type of the BICO parameter.

For CO parameters and BO parameters, only the data type of the BICO parameter is

shown.

Notation:

Data types BICO input: Data type parameter / Data type BICO parameter

Example: Unsigned32 / Integer16

Data types BICO output: Data type BICO parameter

Example: FloatingPoint32
The possible interconnections between the BICO input (signal sink) and the BICO output

(signal source) are listed in the following documents:

References: /LH1/ SINAMICS S List Manual

Chapter "Explanations on parameter list" in table "Possible combinations for BICO

interconnection".

The BICO parameter interconnection can be implemented in different command data sets

(CDS). The different interconnections are activated by switching data sets. Interconnections

across drive objects are also possible.