Basic functions

6.7 Automatic restart (vector, servo, infeed)

Drive Functions

190

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

The starting attempt has been successfully completed if the flying restart and the motor

magnetization (induction motor) have been completed (r0056.4 = 1) and one additional

second has expired. The starting counter is only reset back to the initial value p1211 after

this time.
If additional faults occur between successful acknowledgement and the end of the startup

attempt, then the startup counter, when it is acknowledged, is also decremented.

Monitoring time line supply return (p1213)

The monitoring time starts when the faults are detected. If the automatic acknowledgements

are not successful, the monitoring time runs again. If the drive has not successfully started

again after the monitoring time has expired (flying restart and motor magnetization must

have been completed: r0056.4 = 1), fault F07320 is output. The monitoring is de-activated

with p1213 = 0.
If p1213 is set lower than the sum of p1212, the magnetization time r0346 and the additional

delay time due to flying restart, then fault F07320 is generated at each restart. If, for p1210 =

1, the time in p1213 is set lower than p1212, then fault F07320 is also generated at every

restart attempt. The monitoring time must be extended if the faults that occur cannot be

immediately and successfully acknowledged (e.g. when faults are permanently present).

Commissioning

1. Activating the function for vector and infeed drive object

– Automatic restart: Set mode (p1210).
– Flying restart: Activate function (p1200).

2. Set starting attempts (p1211).
3. Set waiting times (p1212, p1213).
4. Check function.

Overview of key parameters (see SINAMICS S List Manual)

● r0863 CO/BO: Drive coupling status word/control word
● p1207 BI: Automatic restart - connection to the following DO
● p1208 BI: Automatic restart - infeed fault
● p1210 Automatic restart, mode
● p1211 Automatic restart, attempts to start
● p1212 Automatic restart, delay time start attempts
● p1213 Automatic restart, waiting time increment