Safety Integrated basic functions

9.7 Commissioning the "STO", "SBC" and "SS1" functions

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

319

Prerequisites for commissioning the safety functions

1. Commissioning of the drives must be complete.
2. Non-safe pulse disable must be present (e.g. via

OFF1 = "0" or OFF2 = "0")
If the motor holding brake is connected and parameterized, the holding brake is applied.

3. The terminals for "Safe torque off" must be wired.
4. For operation with SBC, the following applies:

A motor with motor holding brake must be connected to the appropriate terminal of the

Motor Module.

Standard commissioning of the safety functions

1. A project that has been commissioned and uploaded to STARTER can be transferred to

another drive unit without losing the safety parameterization.

2. If the source and target devices have different software versions, it may be necessary to

adapt the reference checksums (p9799, p9899). This is indicated by the faults F01650

(fault value: 1000) and F30650 (fault value: 1000).

3. Once the project has been downloaded to the target device, a short acceptance must be

carried out (see table 7-10). This is indicated by fault F01650 (fault value: 2004).

NOTICE

Once a project has been downloaded, it must be stored on the non-volatile

CompactFlash card (copy from RAM to ROM).

Replacing Motor Modules with the current FW release

1. After a Motor Module fails, a more recent firmware release can be installed on the new

Motor Module.

2. If the old and new devices have different software versions, it may be necessary to adjust

the reference checksums (p9899) (see Table 7-2). This is indicated by F30650 (fault

value: 1000).

Table 9-3

Adapting the reference checksum (p9899)

no.

Parameter

Description/comments

1

p0010 = 95

Safety Integrated: set commissioning mode.

2

p9761 = "Value"

Set the safety password.

3

p9899 = "r9898"

Adapt the reference checksum on the Motor Module

4

p0010 = Value not

equal to 95

Safety Integrated: exit commissioning mode

5

POWER ON

Carry-out a POWER ON.

Adapt the reference checksum with the safety screens of STARTER:
Change settings -> Enter password -> Activate settings
After the settings have been activated, the checksums are automatically adapted.