Infeed

1.1 Active Infeed

Drive Functions

26

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

1.1.5

Line and DC link identification

The characteristic line supply and DC link quantities are determined using the automatic

parameter identification routine. They provide the basis to optimally set the controllers in the

Line Module.
An optimal setting of the current and voltage control is achieved with the help of the line

supply and DC link identification routine. The dynamic response of the current control can be

adjusted with p3560.

Note
If the line supply environment changes, or the components connected to the DClink (e.g.

after installing and mounting the equipment at the customer's site or after expanding the

drive group), then the line supply/DC link identification routine should be repeated with

p3410 = 5. Only then can it be guaranteed that the infeed operates with the optimum

controller settings.
When the identification function is activated, alarm A06400 is output.

Identification methods

For additional identification methods, see the SINAMICS S List Manual.
● p3410 = 4: An identification run for the total inductance and DC link capacitance is

initiated when the pulses are next enabled (two measuring routines with different current

magnitudes). Data determined during identification (r3411 and r3412) is entered into

p3421 and p3422 and the controller is recalculated. At the same time, the parameters for

current controller adaptation are determined (p3620, p3622). All of the parameters for the

Infeed Module are then automatically stored in a non-volatile memory.
The infeed continues to operate without any interruption with the new controller

parameters.

● p3410 = 5: The same measurements and write operations are always carried-out for

p3410 = 4. Before the first identification run, however, the parameter values for line

inductance and DC link capacitance are reset (p3421 = p0223 and p3422 = p0227).
p3410 is automatically set to 0 after an identification run has been successfully

completed.

Note
Identification using p3410 = 5 should preferably be used.

It may be necessary to reset the closed-loop controller to the factory settings if an

identification run was unsuccessful, for example.

Overview of key parameters (see SINAMICS S List Manual)

● p3410 Infeed identification method
● r3411 Infeed inductance identified
● r3412 Infeed DC-link capacitance identified
● p3560 Infeed Vdc controller proportional gain